Part 6 – Transformer Connections

Methods of Connecting a Transformer

There are three identical single-phase transformers that can be connected together to form a three-phase transformer. The voltage/amperage formula for a single-phase transformer is: VA = volts (E) x amperes (I), usually in kVA.

Calculating Current in a Transformer

An example of calculating current in a transformer would be:

Consider a 360/720  90 kVA transformer. If 360 V is applied to the primary windings, 720 V will be available at the secondary windings.

The secondary current available would be:

 I (secondary) = \frac{90000 VA}{720V}

 = 125 A

 I (primary) = \frac{90000 VA}{360V}

 = 250 A

A diagram of a 90 kVA single-phase transformer with a 360-volt primary coil and a 720-volt secondary coil.

The voltage/amperage formula for a three-phase transformer is: VA  =  \sqrt 3 \times I_L \times E_L

I_L = line current

E_L = line voltage

Total capacity of the three single-phase transformers connected in a three-phase arrangement:

 3 \times 90 kVA = 270 kVA

Connecting a Transformer

There are two methods of connecting three individual sets of windings in a three-phase transformer, which are the star method and the delta method.

A schematic representation of a star (or wye) connection in a three-phase system with impedance loads Z1, Z2, and Z3. A schematic diagram of a delta connection for a three-phase system with impedance loads ZA, ZB, and ZC.
Star Connection Delta Connection

The star (Wye) method is a three-phase line current that is equal to the current in any one phase. The three-phase line voltage is equal to √3 x the voltage in any one phase. The delta method is a three-phase line voltage that is equal to the voltage in any one phase. The three-phase line current is equal to √3 x the current in any one phase.

Three-phase 225 kVA transformer with both primary and secondary windings connected in Delta.

The current is:

VA  =  \sqrt 3 \times I_L \times E_L

I_L =  \frac{VA}{\sqrt 3  \times E_L}

A delta-delta connection current is:

I_L (secondary) =  \frac{225000 VA}{\sqrt 3  \times 480 V} = 270.6 A

I_L (primary) =  \frac{225000 VA}{\sqrt 3  \times 240 V} = 541.3 A

A schematic for a three-phase transformer, showing voltage levels and calculations for secondary and primary current (I_t), along with the transformer connections providing 240 volts and 480 volts.

Delta-star connection – star provides two voltages: line voltage = 831 V and phase voltage = 480 V. Current is:

I_L (secondary) =  \frac{225000 VA}{\sqrt 3  \times 831 V} = 156.3 A

*Uses line voltage

 

A Step-Down Transformer

Click on the image hotspots to explore the functions of as step-down transformer.

There are only four possible three-phase transformer combinations, which are:

  • Delta to delta
  • Delta to star
  • Star to delta
  • Star to star
A diagram of a three-phase transformer with delta-delta connection, showing the coils connected in delta on both primary (R, Y, B, N) and secondary (a, b, c, n) sides. A diagram of a three-phase transformer with star-star (wye-wye) connection, illustrating the coils connected in a star configuration on both the primary (R, Y, B) and secondary (a, b, c) sides.
Delta-delta connection Star-star connection

The use of delta or star depends on the application. A delta connection is for balanced loads. A three-phase motor is an example of a balanced load in which each of the windings of the motor has identical impedance. It only requires three supply conductors. A star connection is for unbalanced loads and requires four wires.

Unbalanced Load

Click on the image hotspots to explore the functions of an unbalanced load.

Here is a schematic diagram of a three-phase motor connected to a delta-configured transformer, depicting the electrical connection between them.

A schematic of a three-phase motor connected to a delta-configured transformer, depicting the electrical connection between them.

License

PEG-3722 Electrotechnology Copyright © by Josee Beaulieu. All Rights Reserved.

Share This Book