Part 5 – Alternator Cooling Systems

Alternator Cooling Systems

In larger alternators, the increased power and magnetic losses result in higher heat production that must be efficiently managed compared to smaller alternators. The cooling method used directly influences the physical size and structure of these alternators.

Fours types depending on the volt-amp output of the unit:

  • Direct Air
  • Enclosed Air
  • Hydrogen
  • Water

Direct Air Cooling

Small alternators employ rotor shaft-mounted fans for direct air cooling.

Natural Gas Generator

Enclosed Air Cooling

In larger generators, typically ranging from 25 to 325 MVA, enclosed air cooling is the method of choice. This approach involves separate fans to supply cooling air, with air filtration and return ducts designed to direct exhaust air back to the fans’ inlets. Additionally, air coolers with finned tubes circulate cooling water to dissipate heat effectively.

Enclosed Air Cooling

Water Cooling

Certain alternator designs employ water for cooling the stator windings. Cool, deionized water is supplied by a closed-loop auxiliary system and flows through copper strands in the stator winding. This cooling process begins as cool water enters the winding through a distribution header at one end of the generator, and warm water is discharged at the opposite end. Cool, deionized water, provided by a closed-loop auxiliary system, circulates through both the copper strands within the stator winding and the hollow, non-magnetic stainless steel conductors that carry the cooling water.

Water Cooled Alternator
Water Cooled Alternator

Water cooling systems are more complex and more costly than conventional systems, the cost is offset by a significantly smaller physical size.

Activity: Water Cooling

Click the arrows to see images of water cooling systems.

Hydrogen Cooling

Hydrogen cooling is applied in larger alternators, typically those with a capacity ranging from 200 to 1000 MVA. Comparatively, the operation, installation, and maintenance of air-cooled generators are generally more straightforward than those of hydrogen-cooled generators. However, due to the reduced cooling efficiency of air, air-cooled machines of similar ratings require a 20% to 30% increase in size when compared to their hydrogen-cooled counterparts.

Hydrogen Coolers highlighting Stator Core,  Field Winding,   Bearings,   Rotor,   Stator Coil End Support,   Stator Winding,   Collector Rings,   Brush Holders,   Axial Fans,   Retaining Rings,   Bushing CTs,   High Voltage Bushings,   Stator Cooling Water System,   Hydrogen Control System,   Seal Oil System

Advantages of hydrogen gas:

  • High heat transfer coefficient, ensuring efficient cooling.
  • Rapid absorption and rejection of heat as it flows through the generator windings.
  • Lower density than air, requiring less energy for circulation through generator components.
  • Minimizes windage, reducing braking effects on the alternator’s rotating parts.

In hydrogen cooling, the ventilation pattern for a specific design is contingent upon several factors, including the machine’s length and the temperature distribution within its various components, with special attention to the stator and field windings.

Symbol Key to Symbols  XC  Shut Off Valve  X  Non Return Valve  Electrical Connections  Seal  Air Inlet  Valve  Solenoid Valve.  Manually Operated  By-Pass Valve  Perforated Hydrogen Admission Pipe  Gas Cooler  Alternator  Sight Flow  Gauge  Fan Pressure  Chamber  Pressure  Gauge  Outline of Control Chamber  Pressure Switch  Liquid  Alarm  Device  Oil Filter  Differential  Pressure Gauge  with Purity Scale  30" Mercury  "U" Tube  Pressure  Release  Valve  99  Hydrogen Cylinders  Carbon Dioxide Cylinders  Thermometer  Oil Pressure  Switch  Seal  Sight Flow  Gauge  Pressure  Gauge  Bearing Oil Supply Line  Bearing Oil Drain Line  Turbine  Oil Tank  Relief Valve  Drain  Valve  Starter Oil  Pump  Emergency Oil Supply Line  To Atmosphere Outside of Building  Figure 35A  Hydrogen Cooled Generator System  Height-to-Permit-Desired Hydrogen.Pressure  Float  Valve  Hydrogen Detraining Tank

“Once-through” hydrogen cooling configuration highlighting heat exchanger, stator and rotor
“Once-through” hydrogen cooling configuration

In hydrogen cooling systems, there are various designs for gas flow. Some configurations involve gas entry at both ends of the rotor with an exit at the center, while others have entry and exit points at opposite ends. Certain manufacturers employ rotor ventilation slots for gas entry, which then escapes radially through slotted conductors. To mitigate the risk of explosion resulting from hydrogen-air mixing, airtight casings and proper seals around the rotor shaft are employed. Additionally, a CO2 purge system is used.

The importance of keeping hydrogen free from moisture is multifaceted. Moisture can increase the viscosity of hydrogen, reducing its heat-carrying capacity and leading to seal deterioration on the rotating shaft. Thus, hydrogen-cooled machines require effective shaft sealing arrangements to prevent gas leakage.